Use this method when DeltaXStudio can control the conveyor but no calibration camera is installed.

Required: robot + main camera + encoder. DeltaXStudio controls the belt.

Screenshots may show an earlier interface; use the field names in the instructions.

Configure this setup

Stop running tasks and keep Auto Start disabled. Check the robot and main camera connections. Confirm the encoder counts increase with forward conveyor travel.

Disable Calibration Camera in Hardware Settings. Select Camera Fov outside robot area and enable Use Conveyor in Calibration Settings.

Check Conveyor Z and the encoder direction, save, reset, and wait for reconnection.

Calibration Camera disabled in Hardware Settings

Disable the calibration camera and capture robot points manually.

Calibration Settings with Camera Fov outside robot area and Use Conveyor enabled

Select outside-robot camera coverage and enable Use Conveyor for software-controlled belt movement.

Check the working height

Open Settings → Parameters and select the intended robot if more than one is configured.

With the conveyor stopped, use the Dashboard robot controls to approach the belt surface with the installed tool. Reduce the jog increment near the surface and avoid pressing the tool into the belt. Read the robot’s Z coordinate at the belt surface and enter it in Other Parameters → Conveyor Z (mm). This is the field called Z Conveyor in the reference manual.

Set Travel Z (mm), called Z Move in the manual, to a height that clears the carried object, belt, fixtures, and destination throughout the transfer.

Save the settings before calibration. Automatic calibration uses Conveyor Z to calculate approach positions, so check this value for each configured robot.

Other Parameters with Conveyor Z and Travel Z in robot coordinates

Enter the measured conveyor-surface Z and a transfer Z with adequate clearance. The pictured values illustrate one installation.

Dashboard robot jogging controls and Z coordinate readout

Read the current Z coordinate while positioning the installed tool.

Three object heights above the belt can be used as an initial estimate for Travel Z. For example, a belt at Z = -740 mm and a 20 mm object gives -740 + 3 x 20 = -680 mm. Verify the actual clearance and robot reach; this estimate does not account for every tool or fixture.

If a jog command is rejected, check the displayed status, homing state, and configured travel limits before continuing.

Place the board and select the crop

Stop the conveyor and place the supplied board flat under the main camera. Align it with the belt and leave enough travel for the capture sequence. Check that the whole board is visible, sharp, and well lit.

Open Settings → Calibration and click Start. Follow any board-orientation guidance. Select two opposite corners of the detection area in the corrected image. Cover the useful conveyor area. Exclude blank image padding. Click Apply. The system is now ready to capture the reference points.

Calibration board aligned with the conveyor and X offset to its centerline

Keep the board aligned with the belt. X Offset describes the conveyor centerline relative to the robot.

Two opposite corners selected around the camera detection area

Select the useful detection area, then click Apply.

Let the conveyor carry the board between points. Do not lift, slide, or rotate it relative to the belt.

Capture the reference points

  1. Wait while the system captures the camera reference positions and advances to Find Robot Point 1. Follow the prompt to bring the board center into the robot’s reachable area using the Dashboard conveyor controls. Use small position increments near the desired location.
  2. Stop the conveyor. Jog the robot so the center of its tool is directly above the board center. Align X and Y accurately while keeping the tool clear of the board; it does not need to touch the board. Wait until the robot and conveyor are stationary, then click Get Point.
  3. Follow the next conveyor movement prompt. At Find Robot Point 2, align the tool over the board center at its new belt position, wait for motion to finish, and click Get Point again.
  4. Repeat for any remaining robots, then wait for completion and click Done.

Front view of the tool centered above the calibration board

Align the tool center with the board center.

Side view of the tool above the calibration board

Keep the tool clear of the board while aligning.

The two points use the same board center at different encoder positions. Move it with the conveyor rather than moving the board by hand.

Confirm calibration

Wait for successful completion; the system validates and saves the reference points. Click Done, then check the corrected image and crop.

Calibration done confirmation and Done button

Wait for successful completion before clicking Done.

Continue to Vision to verify detection before the first pick. During the first low-speed picking test, check several object positions and conveyor tracking. Repeat calibration after moving the camera, robot, or conveyor relative to one another.

If this calibration cannot finish

Symptom What to check
Board not detected Focus, lighting, board orientation, and complete board visibility.
Crop rejected Select a non-empty area inside the valid corrected image.
Missing or reversed encoder feedback Check the connection and counting direction. Encoder feedback is required for this method.
Board passes the capture area Check available travel and camera-to-robot spacing.
Get Point unavailable or rejected Confirm a manual-point step is active, the robot is connected, and motion has finished with a stationary belt.
Browser reconnects Wait for the current session state to reload before continuing.

Use Stop or Cancel to end the workflow and wait for stopping to finish. Calibration Stop waits for robot motion already in progress; use the physical emergency stop if immediate intervention is needed.